Mineral insulated cables
Fluoropolymer-insulated Heating Cable Factory Terminated
Application:
Vessels, piping, valves
Small components
Industrial areas
Heat tracing on molds
Heat tracing on satellite dishes
Standard:
DIN VDE 0253
Voltage Rating:
230V
CABLE CONSTRUCTION:
Heating conductor
Insulation: Fluoropolymer.
Protective: VA 1.4401 / SS 316.
Mechanical and Thermal Properties:
Maximum operating temperature: 260℃
Minimum installation temperature: -60℃
Minimum bending radius: 2.5xOD
Maximum output: 25 W/m
Cable Parameter:
Heated length m | Nominal output W | ||
---|---|---|---|
Maximum temperature 100 °C | Maximum temperature 150 °C | Maximum temperature 200 °C | |
1.2 |
30 |
- |
- |
2.2 |
54 |
- |
- |
3.4 |
78 |
52 |
26 |
4.8 |
94 |
69 |
37 |
6.0 |
147 |
88 |
44 |
8.4 |
210 |
126 |
63 |
10.8 |
245 |
163 |
82 |
25.0 |
294 |
176 |
88 |
30.0 |
705 |
441 |
220 |
35.0 |
864 |
521 |
- |
42.0 |
1008 |
611 |
315 |
56.0 |
1390 |
756 |
378 |